You can download the Industrial Power Selector chart here.

50 Hz

Net Engine Output

Typical Generator Set Output

1500/1800 rev/min switchable

Litres

Model

Baseload

Prime

Standby

Baseload

Prime

Standby

kWm

kWm

kWm

kWe

kVA

kWe

kVA

kWe

kVA

1500 rpm (6 kVA to 2500 kVA)

        1.1

403A-11G1

8

9

7

9

8

10

        1.5

403A-15G1

12

13

10

13

11

15

403A-15G2

14

15

12

15

13

17

t

        2.2

404A-22G1

18

20

16

20

18

22

        3.3

1103A-33G

28

30

24

30

26

33

tn

1103A-33TG1

42

46

36

45

40

50

tn

1103A-33TG2

54

59

48

60

53

66

tn

        4.4

1104C-44G1

39

43

35

44

38

48

1104C-44TG2

54

59

48

60

53

67

tn

1104A-44TG1

58

64

52

65

57

72

tn

1104A-44TG2

72

79

64

80

70

88

tn

1104C-44TAG1

72

79

64

80

71

89

n

1104C-44TAG2

90

100

81

101

90

112

n

        7.0

1106A-70TG1

118

131

108

135

120

150

1106A-70TAG2

131

144

120

150

132

165

n

1106A-70TAG3

158

175

144

180

160

200

n

1106A-70TAG4

174

191

160

200

176

220

1206A-E70TTAG1

175

192

160

200

176

220

n

1206A-E70TTAG2

201

217

184

230

200

250

n

1206A-E70TTAG3

217

238

200

250

220

275

n

        8.8

1506A-E88TAG4

245

268

226

282

246

308

n

1506A-E88TAG5

268

293

246

308

270

337

n

        9.3

1706A-E93TAG1

299 *

       273 *

275

300

300

330

n

1706A-E93TAG2

306 *

       338 *

320

350

350

385

n

 12.5

2206A-E13TAG2

305

349

280

350

320

400

n

2206C-E13TAG2

305

349

280

350

320

400

n

2206A-E13TAG3

349

392

320

400

360

450

n

2206C-E13TAG3

349

392

320

400

360

450

n

 15.2

2506A-E15TAG1

396

435

364

455

400

500

n

2506C-E15TAG1

396

435

364

455

400

500

n

2506A-E15TAG2

435

478

400

500

440

550

n

2506C-E15TAG2

435

478

400

500

440

550

n

 18.1

2806C-E18TAG1A

514

565

473

591

520

650

n

2806A-E18TAG1A

522

574

480

600

528

660

n

2806A-E18TAG2

565

609

520

650

560

700

n

2806A-E18TTAG4

598

       660

570

712

661

727

n

2806A-E18TTAG5

646

       714

617

771

678

850

n

 23.0

4006-23TAG2A

501

628

691

476

595

597

746

656

820

n

4006-23TAG3A

536

675

756

509

637

641

800

718

900

 30.0

4008-30TAG1

632

758

842

600

750

720

900

800

1000

4008TAG1A

606

767

844

576

720

720

900

800

1000

4008-30TAG2

674

851

947

640

800

808

1010

900

1125

4008TAG2A

681

861

947

647

809

800

1000

880

1100

4008-30TAG3

800

947

1055

760

950

900

1125

1000

1250

 46.0

4012-46TAG0A

842

1053

1158

800

1000

1000

1250

1100

1375

4012-46TWG2A

833

1055

1166

791

989

1000

1250

1100

1385

n

4012-46TAG1A

909

1148

1263

864

1080

1100

1350

1200

1500

4012-46TWG3A

909

1149

1263

864

1080

1100

1350

1200

1500

4012-46TWG4A

1254

1342

1200

1500

1280

1600

4012-46TAG2A

1005

1267

1395

955

1194

1200

1500

1320

1650

n

4012-46TAG3A

1200

1440

1583

1140

1425

1350

1710

1500

1875

 61.0

4016TAG1A

1219

1537

1690

1170

1463

1480

1850

1600

2000

4016-61TRG1

1179

1558

1684

1120

1400

1480

1850

1600

2000

4016-61TRG2

1347

1684

1895

1280

1600

1600

2000

1800

2250

4016TAG2A

1362

1715

1886

1307

1634

1600

2000

1800

2250

4016-61TRG3

1500

1875

2083

1440

1800

1800

2250

2000

2500

t Switchable engines must be requested at point of order, please consult with your local Perkins representative
n Can be switched between 1500 and 1800 rpm
* Engineering targets pending final confirmation, please consult with your local Perkins representative for the latest information

Notes:

  • All ratings are rounded up and are for guidance only, please refer to the specific engine technical data sheet for final powers. – Electrical output is based on assumed alternator efficiency and is for guidance only.
  • kVA figures are calculated using a typical power factor of 0.8.
  • Perkins conditions of sale apply.
  • All ratings data based on operation under ISO 8528-1, ISO 3046, DIN6271 conditions using typical fan sizes and drive ratios. Performance tolerance quoted by Perkins is ± 5%.
  • Prime Power = Unlimited hours usage with an average load factor of 80% of the published Prime Power over each 24 hours period. A 10% overload is available for 1 hour in every 12 hours operation.
  • Standby Power = Limited to 500 hours annual usage with an average load factor of 80% of the published Standby Power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously. No overload is permitted on Standby Power.